Signal Converter KFD2-GUT-EX1.D Pepperl+Fuchs 231225
Signal Converter KFD2-GUT-EX1.D Pepperl+Fuchs 231225

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Canada. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs KFD2-GUT-EX1.D 231225

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KFD2-GUT-EX1.D

Part number

231225

Type

Signal Converter

Description

Temperature Converter with Trip Values KFD2-GUT-Ex1.D

Stock availability:

On request

855.87 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KFD2-GUT-EX1.D 231225

This isolated barrier is used for intrinsic safety applications. The device converts the signal of a resistance thermometer, thermocouple, potentiometer, or voltage source to a proportional output current. It also provides a relay trip value. The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. The device is easily configured by the use of the PACTware configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.

Features KFD2-GUT-EX1.D 231225

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 23+, 24- or power feed module/Power Rail
Rated voltage20 ... 30 V DC
Rated currentapprox. 100 mA
Power dissipation/power consumption&le, 2 W / 2.2 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3, 4, 6
RTDPt100, Pt500, Pt1000, Ni100, Ni1000
Types of measuring2-, 3-, 4-wire technology
Lead resistancemax. 50 &Omega,
Measurement loop monitoringsensor breakage, sensor short-circuit
Thermocouplestype B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)
Cold junction compensationexternal and internal
Measurement loop monitoringsensor breakage
Potentiometer0.8 ... 20 k&Omega,
Types of measuring2-, 3-, 5-wire technology
Voltage0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV
Input resistance&ge, 250 k&Omega, (0 ... 10 V) min. 1 M&Omega, (0 ... 1 V, -100 ... 100 mV)
Measuring currentapprox. 400 µ,A with resistance measuring sensor
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7-
Output I, IIrelay
Contact loading250 V AC / 2 A / cos &phi, &ge, 0.7 , 40 DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output IIIAnalog current output
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 &Omega,
Fault signaldownscale I &le, 3.6 mA, upscale I &ge, 21 mA (acc. NAMUR NE43)
Collective error messagePower Rail
Transfer characteristics
Deviation
Temperature effect Input: 0.005 %/K (50 ppm) of span , current output: 0.005 %/K (50 ppm) of span
RTDmax. 0.2 % of span
Thermocouplesmax. 10µV deviation of CJC: ±0.8 K
Voltage0.1 % of span
Potentiometer0.1 % of span when <5 k&Omega,0.5 % of span when> 5 k&Omega,
Current outputmax. 20 µ,A
Sampling rateapprox. 700 ms
Galvanic isolation
Input/Other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachotherreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective errorreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 03 ATEX 2140
Marking II (1)G [Ex ia] IIC , II (1)D [Ex iaD]
InputEx ia IIC, Ex iaD
Supply
Maximum safe voltage40 V DC (Attention! The rated voltage can be lower.)
Inputterminals 2, 6 (for active equipment)
Voltage13.1 V
Current8 mA
Power67 mW
Voltage29 V
Current11 mA
Power200 mW
Inputsterminals 1, 2, 3, 4, 6 (for passive equipment)
Voltage Uo13.1 V
Current Io21 mA
Power Po67 mW
Output
Contact loading253 V AC/2 A/cos &phi, > 0.7, 40 V DC/2 A resistive load (TÜV 03 ATEX 2140)
Analog output
Maximum safe voltage40 V (Attention! The rated voltage can be lower.)
Interface
Maximum safe voltage40 V (Attention! The rated voltage can be lower.) , RS 232
CertificatePF 08 CERT 1213 X
Marking II 3G Ex nA nC IIC T4 Gc
Output I, II
Contact loading50 V AC/2 A/cos &phi, > 0.7, 40 V DC/1 A resistive load
Galvanic isolation
Input/Other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
IECEx approval
IECEx certificateIECEx TUN 09.0019
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.